L_MC1P_PolePositionIdentification: Drive does not move, depending on call sequence (fixed from V03.21.00)

Corrected from:
Library:  L_MC1P_MotionControlBasic  (FAST Motion)  from V03.21.00.102
                      (Update via Package-Manager)
 
Response of the new version:
The execution of Motion FBs is now possible independently of the xEnable of the FB L_MC1P_PolePositionIdentification and independently of the processing sequence.

 
What happens?
L_MC1P_PolePositionIdentification: Ist der Funktionsbaustein freigegeben, kann keine Motion-Funktion ausgeführt werden.
 
When does the behaviour occur? 
- Execution of the FB 'L_MC1P_PolePositionIdentification' ist released (xEnable = True).
- FB L_MC1P_PolePositionIdentification is in the call sequence before the motion function.
 
Which products are affected?
Library:  L_MC1P_MotionControlBasic  (FAST Motion)

Short-term measures, Evaluation/Recommendations:
Motion functions can be executed if the L_MC1P_PolePositionIdentification is placed at the end of the call sequence of the FBs.
Alternatively the motion functions can also be executed if the FB L_MC1P_PolePositionIdentification is deactivated after the execution of the polling identification (xEnable = False).