Question:
What do you have to observe if you want to use the transmission type 'asynchronous - device-profile-specific' for analog input modules at an I/O 1000 bus coupler (EPM-S110)?
 
Answer:
First, you have to change the parameter 0x6423 to 255.
Error Event Driven Analog Inputs.bmp 
Meaning: Global activation/deactivation of the event-controlled process data transfer of the analog input signals. The setting in 0x6423 has a higher priority than the settings in the TxPDOs.
 
In addition, you also have to have change the value in the parameter 0x6421 to 7.
Trigger selection.bmp
Meaning: This setting enables the interrupt for analog inputs / outputs.
 
And finally, you have to set the transmission type of the analog input PDO to 255 (asynchronous - device-profile-specific).
 
Only after these changes, an asynchronous input PDO will be transmitted in the case of a value change.