Oscilloscope does not trigger in the case of digital signals and "Value change" trigger mode.

Corrected from:
Inverter Drives 8400 StateLine V16.00.00
Inverter Drives 8400 HighLine V16.00.00
Inverter Drives 8400 TopLine V16.00.00

Inverter Drives 8400 protec HighLine V16.00.00


Response of the new version:
The trigger of the oscilloscope also works with digital signals and the "Value change" trigger mode.


What happens?
The trigger is not activated. As a result, recording does not start.

When does this behaviour occur?
The behaviour occurs when triggering on digital signals and the "Value change" trigger mode is selected.
 
Which products are affected?
Inverter Drives 8400 StateLine FW < V16.00.00
Inverter Drives 8400 HighLine FW < V16.00.00
Inverter Drives 8400 TopLine FW < V16.00.00

Inverter Drives 8400 protec HighLine FW < V16.00.00
 
Short-term measures:
Connect a BitToWord converter to the digital signal in the FB interconnection and trigger on its output.

Evaluation/recommendations:

If the current state is known, positive or negative trigger mode selection is possible to start recording if the value changes.

 