Eliminated from: i700 servo inverter V01.03.08.9047
Behaviour of the new version: The above parameter settings are correctly saved together with the PLC Designer project and using 'Create boot application' stored in the controller so that changes will still be available after mains switching.
What happens? For the following parameters, the selected settings are no longer available after mains switching although PLC program and parameters were stored in the controller ('Create boot application'):
- 0x2826 Quick stop: Duration in case of trouble
- 0x2BA0 Flying restart: Activate
- 0x60C0 Interpolation sub mode select
- 0x6048 Acceleration ramp
- 0x6049 Deceleration ramp
- 0x10F1:2 Synchronisation error counter – monitoring limit
When does the problem occur? The problem occurs whenever the drive system is switched on.
Which products are affected? i700 servo inverters ≤ V01.02.04.8817
Short-term measures/recommendations: Initialise parameters via the PLC program with the required settings whenever the i700 is switched on.
Evaluation: Simple remedy available.