Download with L-force Loader via parameter channel 2 - Abort on change of CAN node address (C0350) (eliminated as of SPLC V8.0, ECS and DPLC as of V8.3)

Eliminated from:
EVS93xx-EI (Servo PLC V8.0)
EVS93xx-ET (Servo PLC V8.0 with technology function)
ECS Application operating software from V8.3 onwards
EPL-10200 (Drive PLC V8.3)

Behaviour of the new version?
If the CAN node address has been changed under C0350 the parameters are downloaded correctly by means of the L-force Loader via parameter channel 2.



What happens?
When using the L-force Loader to download parameters via parameter channel 2 , the connection to the PLC target system is aborted. The parameter set is not transmitted completely.

When does the problem occur?
The problem occurs when using the L-force Loader to download a parameter set via parameter channel 2 if, compared to the PLC target system, another value is set in the GDC file under code C0350 (node number). When writing to code C0369 the node number which has already read in is adopted for parameter channel 2 in C0350. As a result, the communication is aborted.

Which products are affected?
ECS Application operating software V8.0 and lower
EPL-10200 EI (Drive PLC) V8.2 and lower
EVS93xx-EI (Servo PLC V8.0 and lower)
EVS93xx-ET (Servo PLC V8.0 and lower with technology function)

Possible diagnostics?
Observe the L-force Loader messages.

Short-term measures/recommendations?
Use CAN parameter channel 1.

Evaluation:
Remedial measure available.

CR Id 1: LDS00024371, Failure Report Id: 8629 CR Id 2: LDS00023707, Failure Report Id: 8419 CR Id 3: LDS00021533, Failure Report Id: 7930
Published with Service Message No. 2010/32, 2011/02 and 2011/31

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201010963/1/