Incorrect representation of bit 2 and 3 in the FB CAN1-IN of the 8200 vector / motec (remedied from V4.10 SP4)

Remedied from?
GDC V4.10 SP4

Behaviour of the new version?
With Service Pack 4 for GDC version 4.10, the CAN1-IN output bits are display correctly.



Which products are affected?
GDC V4.10 SP2 in combination with 8200 vector / motec and CAN fieldbus function module

What happens?
The output bits 2 and 3 (W1-Bit2 and W1-Bit3) at the CAN1-IN function block have been mixed up and are therefore represented incorrectly.

When does the problem occur?
If the function block is used to interconnect function blocks.

Possible diagnostics?
The two bits are only mixed up at the function block. If the bits have been assigned via codes C0410, C415, C0417 and C0418 this is the 'valid' (decisive) assignment.

Short-term measures/recommendations?
Do only use the codes C0410, C415, C0417 and C0418 to parameterise the two output bits (W1-Bit2 and W1-Bit3) of the CAN1-IN function block.

Evaluation:
Due to the internally mixed up output bits (W1-Bit2 and W1-Bit3) of the CAN1-IN function block it may happen that the drive behaves incorrectly. This maloperation has been eliminated with SP 4 for GDC version 4.10.