8200 vector/motec: Code C0360 and the parameter set transfer (remedied from V4.7)

Remedied from?
GDC 4.7 and GDC easy 4.7

Behaviour of the new version?
If code C0360 of an 8200 vector/motec is transferred during the parameter set transfer, a CAN Reset Node is not activated and the communication features of the device are not changed.



Which products are affected?
GDC 4.6.1 und GDC easy 4.5

What happens?
If code C3060 of an 8200 vector/motec is transferred during the parameter set transfer, a CAN Reset Node is activated and the communication features of the device are changed. This happens in case of the 8200 vector/motec with software version ≥ 2.1

When does the problem occur?
When transferring parameter sets.

Possible diagnostics?
Since the transfer of code C0360 activates a CAN Rest Node communication, disturbances may occur due to parameter changes. If these disturbances occur in combination with a parameter set transfer, this may indicate that the error described above has occurred.

Short-term measures/recommendations?
The error has been eliminated with GDC 4.7 and GDC easy 4.7.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/200414112/1/