No connection to the optional fieldbus modules 'EtherCAT Slave' and 'PROFINET IO Device' (fixed from V1.15)

     

Fixed from:
Controller c520 (from FW V01.15.0)
Controller c550 (from FW V01.15.0)
(Update via Easy Package Manager and firmware loader)

Behavior of the new version:
All fieldbus modules are recognized as intended and the fieldbus function is given.
Furthermore, separately supplied modules produced from 01/2026 are also recognized in all firmware versions (also < FW 1.15.0).

 


Description of the behavior:
The plugged-in fieldbus modules
  • EtherCAT Slave (Mat-No. 13657829; type C5MAFT000000)
  • PROFINET IO Device (Mat.No. 13657828; type C5MAFR00000000)
are not recognized by the controller.

In the parameters
  • 0x231F:001 (Module ID: Active module ID)
  • 0x231F:002 (Module ID: Connected module ID)
the value "No fieldbus [48]" is displayed and the fieldbus does not work.
EtherCATSlave_KeineModulID2.png

Conditions under which the behavior occurs:
Only separately purchased fieldbus modules can exhibit this behavior.
Modules that are already plugged into the controller on delivery do not.
Only modules produced in the period between 10/2025 and 12/2025 are affected.

Affected products:
Controller c520 (with FW <= V1.14)
Controller c550 (with FW <= V1.14)

Short-term measure, recommendations, evaluation:
Contact the Lenze Service.


URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202500420/1/