L_TT1P, L_MC1P, L_MC2P: The internal visualisations cannot be used (corrected from V3.26.1)

Corrected from:
L_TT1P_TechnologyModules_LM (from V03.26.01)
L_MC1P_MotionControlBasic (from V03.26.01)
L_MC2P_MotionControlCam (from V03.26.01)
L_CT1P_ControlToolbox (from V03.26.01)
L_USPP_SignalProcessing (from V03.26.01)

Response of the new version:
The visualisations can now be used


What happens?
The visualisations are faulty and not usable.

When does the behaviour occur?
Integration of the visualisation from the library for a function block leads to an error in the visualisation:
Visualisation [Device: PLC Logic: Application]: context: no signature
Object reference not set to an instance of an object.

Which products are affected?
All technology modules from library L_TT1P_TechnologyModules_LM (only V03.26.00.16)
Functions from library L_MC1P_MotionControlBasic (only V03.26.00.200)
Functions from library L_MC2P_MotionControlCam (only V03.26.00.33)
Functions from library L_CT1P_ControlToolbox (only V03.26.00.41)
Functions from library L_USPP_SignalProcessing (only V03.26.00.14)

Short-term measures:
The libraries V03.25.xx.xx or older can be used. This means that the internal visualisations can be operated.

Evaluation / recommendations:
The visualisation is used during commissioning. If the visualisation is not functional, it leads to a restriction or extension of the commissioning of applications.