L_TS2P_FlexCamState: Output wActiveCamTable becomes 0 (corrected from V3.26.0)

Corrected from:
Library:  L_TS2P_TechModulesSynchronizingCamming (from V3.26.0)
                      (Update via EASY Package-Manager)

Response of the new version:
As soon as the TM FlexCam is activated (xEnable = TRUE) it shows a valid value at the output wActiveCamTable.
 
What happens?
The TM FlexCam displays an invalid value at the output wActiveCamTable = 0.

When does the behaviour occur?
The TM FlexCam is in the STANDBY state.

Which products are affected?
TM FlexCAM (L_TS2P_FlexCAMState from library L_TS2P_TechModulesSynchronizingCamming)

Short-term measures:
The output wActiveCamTable is updated in the CAMING state. It should therefore only be evaluated in this state.

Evaluation / recommendations:
When switching to the STANDBY state, the wActiveCamTable output is initialised and no longer updated. The wActiveCamTable output is only used for status information of the TM and has no influence on the function.