L_MC1P: Touch probe (TP) and external position encoder: encoder zero pulse cannot be evaluated as touch probe (TP) (corrected from V03.26.00)
Corrected from:
Library: L_MC1P_MotionControlBasic (FAST Motion) from V03.26.00
(Update via Package Manager)
Response of the new version:
i950: The zero pulse from the external position encoder at i950 slot B can now also be evaluated as a position source for the touch probe function 'MC_Touchprobe'.
What happens?
Touch probe function and external position sensor (application feedback):
Using the zero pulses from the second encoder at i950 slot B as a position source for the touch probe function does not work.
The message "InvalidTpSource" is displayed at the ErrorID output.
When does the behaviour occur?
Encoder axis serves as position source for the touch probe function (encoder axis at axis input of FB 'MC_Touchprobe')