Commissioning function "PLI without movement":
Depending on the parameterisation of the synchronous motor, the overcurrent monitoring may respond when the test pulses are output.
With the synchronous motors of the M850 series, the setting of parameter 0x2C01:3 is relatively large because this value is specified for operation in no-load operation (motor current approx. 0A). This increases the probability of the overcurrent threshold being reached.
Background:
The pulse widths of the test pulses are calculated via the current DC voltage in the DC link and the set stator inductance (0x2C01:3).
If the stator inductance is set too high, wider pulses result, which can cause the current to rise to the overcurrent threshold in unfavourable cases.
In normal operation in servo control, the product of stator inductance (0x2C01:3) and saturation characteristic (0x2C04) is always effective, whereby a balance is established.
This compensation does not yet take place in a similar way with the PLI function.