PROFINET / EtherCAT / EtherNet/IP: Fieldbus-specific IP addresses and parameterisations are lost after firmware update to V01.07.04 (corrected from V01.07.05)

​​​Corrected from:
Servo Inverter i950 FW: from V01.07.05
 
Response of the new version:
When updating the firmware to V01.07.05, the remanently stored fieldbus-specific IP addresses, Profinet station names and parameterisations are now retained.

 
What happens?
When updating the firmware (FW update) to version V01.07.04, the remanently stored fieldbus-specific IP addresses, Profinet station names and parameterisations are lost. The default values are then effective, so that the units are typically no longer accessible from the master.

Affected parameters:
  • PROFINET: Station name (0x2381:004)
  • PROFINET: IP address (0x2381:001)
  • PROFINET: subnet mask (0x2381:002)
  • PROFINET: gateway address (0x2381:003)
  • PROFINET: I&M1-4 data (0x2381:005..009)

  • EtherCAT: SII EEPROM content, including Configured Station Alias

  • EtherNet/IP: IP configuration (parameter 0x23A1:005)
  • EtherNet/IP: IP address (0x23A2:001)
  • EtherNet/IP: subnet mask (0x23A2:002)
  • EtherNet/IP: gateway address (0x23A2:003)
  • EtherNet/IP: ACD address conflict detection (0x23A7:000)
  • EtherNet/IP: Timeout (0x23A1:010)
  • EtherNet/IP: Rated Current (0x6075:000)
  • EtherNet/IP: Rated Voltage (0x2C01:007)
  • EtherNet/IP: Motor Type (0x5020:026)
  • EtherNet/IP: Multicast TTL (0x23A1:006)
  • EtherNet/IP: Multicast Assignment (0x23A1:007)
  • EtherNet/IP: multicast IP address (0x23A1:008)
  • EtherNet/IP: multicast number (0x23A1:009)
  • EtherNet/IP: Ethernet port 1 setting (0x23A4:001)
  • EtherNet/IP: Ethernet Port 2 Setting (0x23A4:002)
When does the behaviour occur?
  • Use of a PROFINET, EtherCAT or EtherNet/IP fieldbus module and
  • i950 firmware update to version V01.07.04

Which products are affected?
Servo Inverter i950 FW, only V01.07.04 affected
 
Short-term measures / Evaluation / recommendations:
Manual reconfiguration of the fieldbus-specific IP addresses and parameterisations to be stored remanently using Lenze Easy-Starter.