EtherCAT Master i950 reports warning "Fieldbus: Invalid process data", warning message cannot be reset (corrected from V01.05.02)
Corrected from:
Servo-Inverter i950 FW: from V01.05.02.1788
Response of the new Version:
After starting the i950 no error message "Fieldbus: Invalid process data", ID: 0x31038193, severity "Warning" is now entered in the logbook.
Monitoring is now only active when the EtherCAT status 0x2368 = "Operational [8]" is reached.
What happens?
After starting the i950 with default values the error message "Fieldbus: Invalid process data", ID: 0x31038193, Severity "Warning" is entered in the logbook.
When does the behaviour occur?
When an EtherCat module is plugged in and the EtherCAT status is not 0x2368:0 = "Operational [8]".