The motor starts after acknowledging an undervoltage error although the auto-start lock function is activated for this error. The motor should only start after an edge change of controller enable.
When does this behaviour occur?
Setting "Resp. to DC bus voltage" (C600/1 = 1) "Fault" and "Inhibit at undervoltage"(bit 3) for "Auto-start option" (C142:0).