L_MC1P - MC_MoveAbsolute: For target positions > 360°, the selected direction of rotation is not observed as expected (corrected from V3.13.0)

Corrected from:
Library: L_MC1P_MotionControlBasic (FAST Motion)  V03.13.00.38 
                      (contained in the PLC Designer from V03.13.00) 

Response of the new version:
Behaviour of MC_MoveAbsolute when using a modulo axis
Example: Modulo cycle = 360 units = 360°
StartPosTargetposMotionStartPosTargetposMotionStartPosTargetposMotion
MC_DIRECTION         
mcCurrentDirection := 0,00no motion0360no motion0720no motion
mcPositiveDirection := 1,00no motion0360no motion0720no motion
mcNegativeDirection := 2,00no motion0360no motion0720no motion
mcShortestWay := 3,00no motion0360no motion0720no motion
mcPositiveCycle := 11,00no motion0360 +360°0720+720°
mcNegativeCycle := 1200no motion0360 -360°0720-720°
StartPosTargetposMotionStartPosTargetposMotionStartPosTargetposMotion
MC_DIRECTION         
mcCurrentDirection := 0,090+90°0300+300°0450+90°
mcPositiveDirection := 1,090+90°0300+300°0450+90°
mcNegativeDirection := 2,090-270°0300-60°0450-270°
mcShortestWay := 3,090+90°0300-60°0450+90°
mcPositiveCycle := 11,090+90°0300300°0450+450°

 

mcNegativeCycle := 12090-270°0300-60°0450

-630°

 
 
 
What happens?
In the modulo measuring system, the target position is not approached as expected.
Example:
- The modulo axis is at position 0 units.
- The MC_MOVEABSOLUTE FB shall be used to travel to the target position 370 units, with negative direction of rotation.
- Actually, it is positioned to position 10 with positive direction of rotation.
 
When does this behaviour occur?
  • Modulo measuring system and
  • target position > 360° (modulo cycle) and
  • negative direction of rotation is selected
Which products are affected?
Library:  L_MC1P_MotionControlBasic (FAST Motion)
                      (contained in the PLC Designer)
 
Short-term measures:
Select target positions smaller than one modulo cycle or use the 'MC_MoveRelative' FB. 
 
Evaluation/recommendations:
 

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201600005/1/