L_MC1P - L_MC1P_MeasureDistance: Distance measured with modulo measuring system is not correct (corrected from V3.12.0)

Corrected from:
- Library: L_MC1P_MotionControlBasic (FAST Motion) V03.12.00.xxxxx
  (contained in PLC Designer as of V03.12.00)
 
Response of the new version:
If the 'L_MC1P_MeasureDistance' FB is used with a modulo axis, the measured distance values are correct now. 
 
What happens?
If the 'L_MC1P_MeasureDistance' FB is used with a modulo axis, the measured distance values are not correct.
 
When does this behaviour occur?
- The behaviour occurs when using the 'L_MC1P_MeasureDistance' FB with a modulo axis (modulo measuring system).
 
Which products are affected?
- Library: L_MC1P_MotionControlBasic (FAST Motion)
  (contained in the PLC Designer)
 
Short-term measures:
Calculate the distance to be measured in the PLC application.
 
Evaluation/recommendations:
 