Corrected from:
Library: L_MC1P_MotionControlBasic (FAST Motion) V03.17.00.226
(update via package manager)
Response of the new version:
The described function restriction is remedied now.
What happens?
Under certain conditions, the MC_Touchprobe FB does not work correctly.
No measured value and no 'xDone' signal is reported.
When does this behaviour occur?
TouchProbeMode = 1 (single measurement) and
TouchProbeEdge = 5 (first positive and then negative edge) or
TouchProbeEdge = 6 (first negative and then positive edge)
Which products are affected?
Library: L_MC1P_MotionControlBasic (FAST Motion)
(contained in the PLC Designer)
Short-term measures:
Use the TP operating modes TouchProbeEdge = 1 or 2 instead of TouchProbeEdge = 5 or 6 and simulate the evaluation logic in the application.
Evaluation/recommendations:
A short-term remedy is available.