L_MC1P - L_MC1P_MeasureDistance: FB does not work correctly when performing the modulo transition (corrected from V3.12.0)

Corrected from:
- Library: L_MC1P_MotionControlBasic (FAST Motion) V03.12.00.70
  (contained in PLC Designer V03.12.00.177 and higher)

Response of the new version:
The L_MC1P_MeasureDistance FB works correctly in the modulo measuring system.

What happens?
In the modulo measuring system, the cycle return is not considered correctly. Therefore, incorrect values are output at the lrDistance output of the 'L_MC1P_MeasureDistance' FB.
When does this behaviour occur?
  • The behaviour occurs if the "Modulo" measuring system has been selected for an axis. 
Which products are affected?
- Library: L_MC1P_MotionControlBasic (FAST Motion)
  (contained in the PLC Designer)
 
Short-term measures:
None.
 
Evaluation/recommendations:
 