Automatic switch-over to V/f without encoder as emergency operation
Which products are affected? Inverter Drives 8400 StateLine, HighLine and TopLine from firmware version 15.01.00.00
Functional description In order to avoid impermissible motor movements in the case of an open encoder circuit in a motor control type with feedback, an internal switch-over to V/f without encoder is effected. This can be configured via C02864/001 bit08: 0 = V/f emergency operation in the case of an open encoder circuit (default) 1 = no V/f emergency operation in the case of an open encoder circuit This has no impact on the setting in C00006. For the 2-track HTL and SSI speed feedbacks, definite detection of an open circuit is not possible, and there is no switch-over to emergency operation in the event of an error.
Taxonomy:
8400 StateLine frequency inverters
,
8400 HighLine frequency inverters
,
8400 TopLine frequency inverters
AKB-ID:
201500439
Last update:
2023/09/09