L_MC2P - MC_GearInPos: 'InvalidInputData' message although no modulo measuring system is selected (corrected from V3.10.0)
Corrected from: - Library: L_MC2P_MotionControlCam (FAST Motion) V03.10.00.56 (contained in PLC Designer V03.10.00.00 and higher)
Response of the new version:
The selected measuring system will be considered when checking the input parameters.
What happens?
If the MasterSyncPosition is set to a value higher than the modulo cycle set in the Axis_Ref in a limited measuring system, the 'MC_GearInPos' FB reports the 'InvalidInputData' error. As a result, the clutch process cannot be started.
When does this behaviour occur?
- The measuring system of the master axis is set to 'Limited'. - MasterSyncPosition is higher than the modulo cycle selected in the Axis_Ref (subindex 031).
Which products are affected? - Library: L_MC2P_MotionControlCam (FAST Motion)
(contained in the PLC Designer)
Short-term measures:
Set the cycle of the Axis_Ref (subindex 031) to a value higher than the MasterSyncPosition to be used.