L_TT1P_WinderDancerCtrl (State, High): Measuring point MP1_lrDancerPosScaled0To1 supplies incorrect values

Eliminated from:
L_TT1P_TechnologyModules_SM3 V3.9.0.9
L_TT1P_TechnologyModules_LM V3.9.0.62
 
Behaviour of new version:
The measuring point MP1_lrDancerPosScaled0To1 shows valid values.
 
What happens?
The MP1_lrDancerPosScaled0To1 element of the scSignalFlow technology module output does not indicate the scaled dancer position.
 
When does this behaviour occur?
The above-described behaviour occurs if the L_TT1P_WinderDancerCtrlState or the L_TT1P_WinderDancerCtrlHigh technology module is in the eTMState = DancerCtrl state.
 
Which products are affected?
PLC Designer from V3.8
L_TT1P_TechnologyModules library V3.8.0.23
 
Short-term measures/recommendations:
To calculate the scaled dancer position, divide the value of the measuring point scSignalFlow.MP1_lrDancerPosScaled0To1 by the material length scPar.lrMaterialLength.
 
Evaluation:
The measuring point scSignalFlow.MP1_lrDancerPosScaled0To1 indicates an incorrect value. This function restriction does not impair the actual function of the technology module. An applicative solution is described under "Recommendations". The function restriction does not concern the L_TT1P_WinderDancerCtrlBase technology module.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201400218/1/