Direction of rotation control (0x2825=4): Setpoint current is sporadically not reached (corrected from V1.6.3)

Corrected from: 
- i700 servo inverter V01.06.03.9953 

Response of the new version:
The 'Direction of rotation control' commissioning function (0x2825=4) works as expected.
 

What happens?
Sporadically, the motor cannot be rotated by means of the 'Direction of rotation control' (0x2825=4) commissioning function.

 

When does the problem occur? 
The setpoint current required as a condition to start the acceleration ramp of the output frequency is sporadically not reached. As a consequence, the motor does not rotate. 

Which products are affected?
- i700 servo inverter ≤ V01.05.06.9665

Short-term measures/recommendations:
Increase the setpoint current parameter (0x2836:1). After inhibiting the controller and enabling it again, the motor can usually be rotated again.

Evaluation:
The 'Direction of rotation control' commissioning function is only used during commissioning or in the case of servicing.
Therefore, the function restriction is not relevant for normal system operation.
 