EtherCAT Bus reports ¨Master set Operational failed 0x4000007¨(eliminated from 3200 C/p500 V3.6)
Eliminated from:
3200 C, p500 controller V3.6 and higher
Behaviour of the new version:
The EtherCAT bus can be restarted with xRestart without error message.
What happens? The EtherCAT master displays the following error message: Master set Operational failed 0x4000007
The error message can only be reset by switching the mains of the controller.
When does the problem occur? If the EtherCAT bus is restarted via xRestart very shortly after the program start, the above-described response occurs sporadically.
Which products are concerned? 3200 C, p500 controller from V3.5
Possible diagnostics: None
Short-term measures/recommendations: None
Evaluation: When the controller is switched on, the program start also starts the EtherCAT bus. This means, in this case, a restart of the EtherCAN bus activated via xRestart is not necessary. If a restart of the EtherCAT bus is activated directly after the program has been started, this may cause an error message which can only be reset by switching the mains of the controller.
Taxonomy:
Controller 3221 C
,
Controller 3231 C
,
Controller 3241 C
,
Controller 3251 C
,
Controller 3200 C
,
Controller p500
AKB-ID:
201302931
Last update:
2023/09/09
Category:
Version Informations
Lenze reserves the right to change information on this page at any time. Any liability for the accuracy of the information is excluded.