Which products are affeced?
PLC Designer from V3.3
When does the problem occur?
The following error message is indicated during the project compilation:
bSWEndSwitchActive is no AXIS_REF_xxx component
What happens?
In the AXIS_REF_SM3 drive interface the bSWEndSwitchActive (BOOL) variable has been renamed to usiSWEndSwitchActive (USINT) in order to show the state of its activation.
Possible diagnostics?
None.
Short-term measures/recommendations?
Use the xSwLimitSwitchActive output of the L_SMC_AxisBasicControl function block to evaluate the software limit switches.
Evaluation:
An element of the AXIS_REF_SM3 drive interface has been changed in an incompatible way. The function restriction occurs if the bSWEndSwitchActive variable is accessed from the PLC program. The libraries included in the scope of supply of the PLC Designer are not affected by this function restriction.