The EtherCAT master does not start the EtherCAT (eliminated from 3200 C/p500 V3.6)
Eliminated from: 3200 C controller V3.6 p500 controller V3.6
Behaviour of the new version:
The EtherCAT master starts reliably even if in case of a boot project the EtherCAT is restarted shortly after starting the PLC application.
What happens? The EtherCAT does not start. The EtherCAT slaves do not change to the 'operational' state. The EtherCAT node is indicated with a red triangle in the PLC Designer.
When does the problem occur? If in case of a boot project the EtherCAT is restarted (EtherCAT_Master.xRestart:=TRUE) shortly after starting the PLC application has been started it may happen that the EtherCAT master is not started.
Which products are affected? 3200 C controller from V3.2 p500 controller from V3.3
Possible diagnostics? The IPC or PLC logbook does not include the message