Manual inputs for actuating drive speed without function (eliminated in 8400 HighLine and StateLine from V11.0, TopLine from V02.0)
Eliminated as of:
8400 StateLine with firmware version V11.00
8400 HighLine with firmware version V11.00
8400 TopLine with firmware version V02.00
Behaviour of the new version?
The inputs were renamed and are now offered as free user inputs.
They do not have a pre-assigned function.
What happens?
The control of signals LA_Nctrl_bManJogPos and LA_Nctrl_bManJogNeg does not influence the drive behaviour of the 'Actuating drive speed' application.
When does the problem occur?
When the digital functions of the application are used.
Which products are affected?
8400 StateLine with firmware version all versions ≤ V06.xx
8400 HighLine with firmware version all versions ≤ V10.xx
8400 TopLine with firmware version all versions V01.xx
Diagnostics options?
The drive does not change to the manual jog function.
Short-term measures/recommendations?
Manual jog can be carried out via e.g. jog values.
Evaluation:
The functional test of these signals is carried out during commissioning and the problem is detected immediately because the drive does not rotate.
Taxonomy:
8400 HighLine frequency inverters
,
8400 StateLine frequency inverters
,
8400 TopLine frequency inverters
AKB-ID:
201205314
Last update:
2023/09/09
Category:
Version Informations