Zero pulse generation in case of DFOUT is not deactivated after changeover of the DFOUT function via C0540 (remedied from V7.0 in 9300ES)

Which products are affected?
9300ES servo controller V7.0

Eliminated function restriction
The generation and display of zero pulses at the master frequency output X10 via the DFOUT-function is activated and deactivated correctly now, dependent on the selected DFOUT mode under C0540.




Which products are affected?
9300 ES servo controller <= V6.2
9300EP position controllers as of V8.0
9300 EK CAM <= V7.1

What happens?
The master frequency output X10 continues to show zero pulses, although the DFOUT function under C0540 has been changed over to a mode without zero pulse output.

When does the problem occur?
After switch over from a mode with zero pulse output to another one without zero pulse output, e. g.: from C0540 = 2 to C0540 = 1.
If you switch on with C0540 = 1 (without zero pulse output), no zero pulse is displayed at X10.

Possible diagnostics?
After changing over the DFOUT function C0540 zero pulses are continued to be displayed at X10.

Short-term measures/recommendations?
After changing the DFOUT function under C0540 store the settings under C0003 and execute mains switching.

Evaluation:
The behaviour occurs during commissioning only and can easily be eliminated by mains switching.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/200701899/1/