Torque control: operation not possible because automatic DC injection braking is activated
Question:
Why does the drive fail to rotate despite analogue torque setpoint?
Answer:
The drive controller is not receiving any torque setpoint and it is still in automatic DC injection braking . By deactivating the auto appliance protection and control function with C0019 = 0 or C0106 = 0 the drive leaves STOP mode and ramps with the specified torque setpoint up to the torque parenthesised value from C0011.