After creating a boot application, it is no longer possible to log in via PLC Designer

     

Fixed as of: 

 

Behavior of the new version: 

 


Description of the behavior:
 

If encrypted communication between PLC Designer and the controller is enabled, creating a boot application with a new device name results in the inability to establish a connection after the controller is restarted.


Conditions under which the behavior occurs:
 

Encrypted communication enabled

Renaming the device while creating a boot application


Affected products:
 

PLC Designer 4.2


Short-term measures, recommendations, assessment:
 

Action 1

  • Delete the gateway you are using.
  • Add the device’s gateway again, and then connect to the device.
  • After that, the new certificate can be accepted.

Action 2
  • Select another available gateway and use it to connect to the target device.
  • This will allow the new certificate to be accepted.
[Automatic Translation]
URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202600240/1/