Fixed as of:
Cabinet Controller c520 V1.15.2
Cabinet Controller c550 V1.15.2
Behavior of the new version:
The Profinet module of the Lenze controller processes the PDO data correctly.
Description of the behavior:
- The higher-level Profinet master displays error messages during process data communication.
- No PDO data is exchanged between the Lenze controller and the Profinet master.
- The PDO data is not displayed correctly in PLC Designer.
- The Lenze controller does not report any error messages regarding Profinet communication.
Conditions under which the behavior occurs:
The behavior described above occurs when the Lenze controller communicates with a Profinet master via its Profinet interface and the Lenze controller is running firmware version 1.15.1.
Affected products:
Cabinet Controller c520, version 1.15.1 and later
Cabinet Controller c550, version 1.15.1 and later
Short-term measures, recommendations, assessment:
Use the EASY Firmware Loader to update the Lenze controller’s firmware to version 1.15.0 or, as soon as it becomes available, to version 1.15.2.
There is no alternative workaround for a Lenze controller with firmware version V1.15.1.