No parameter set download after restarting a HotConnect participant

     

Fixed as of: 

Cabinet Controller c430 V1.15.2

Cabinet Controller c520 V1.15.2

Cabinet Controller c550 V1.15.2

 

Behavior of the new version: 

After a HotConnect node is restarted, the Lenze controller loads the appropriate parameter set into that node.  

      

Description of the behavior: 

After an EtherCAT node is powered on, the Lenze controller does not transfer the necessary parameter set to that node.


Conditions under which the behavior occurs: 

The behavior described above occurs when

  • the EtherCAT node has been configured in a HotConnect group and
  • this EtherCAT node is not in the primary HotConnect group, and
  • once this EtherCAT node has been operational, it is subsequently restarted, e.g., by cycling the power. The restart resets the EtherCAT node’s parameters to their default values, and due to this functional limitation, the controller does not retransmit the parameter set.

Affected products:

Cabinet Controller c430

Cabinet Controller c520

Cabinet Controller c550

Short-term measures, recommendations, assessment: 

Restart the entire EtherCAT bus.
[Automatic Translation]
URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202600165/1/