PID ramp time is incorrect

     

     

Fixed as of: 

 4.7.0.13

Behavior of the new version: 

 

The ramp time is now correctly reset after the inverter is disabled.

 

Description of the behavior: 

After inverter is inhibit and a restart, the ramp time of the PID controller is not correctly taken into account.


Conditions under which the behavior occurs: 

 

Use of the PID controller.

 

Short-term measures, recommendations, evaluation: 

A minimum wait time of 50 ms must be observed between two starts.