Corrected from:
-
Behavior of the new version:
-
Description of the behavior:
The following exception occurs when starting commissioning sequence:
Could not load file or assembly 'CommissioningSequence...
Conditions under which the behavior occurs:
An exception occurs if the PLC Designer is logged in to a Lenze controller and if the commissioning sequence is started by pressing the button <Start sequence> in the commissioning sequence dialog on the settings tab of the inverter for an servo inverter i750 or i950 (from V1.7) connected to the EtherCAT master.
Affected products:
PLC Designer from V4.1
AddOn: Lenze Device Family i9xx from V4.1
Short-term measure, recommendations, evaluation:
Use PLC Designer V4.0.1.