Controls - DateTimeVarIn: If DateTimeMode = TimeOnly or DateOnly, the value is not written directly to the PLC

     

Corrected from: 

 

Behavior of the new version: 

 

Description of behavior: 

If a DateTimeVarIn is used with the setting that only the date (DateTimeMode = DateOnly) or only the time (DateTimeMode = TimeOnly) is displayed, the value is only transferred to the PLC if the user clicks outside the control after entering it.


Conditions under which the behavior occurs: 

  • Use DateTimeVarIn with the setting DateTimeMode = DateOnly or TimeOnly
  • Change the value at runtime

 

Affected products: 

EASY UI Designer 1.8

 

Short-term measures, recommendations, assessment: 

Use DateTimeVarIn with the setting DateTimeMode = DateTime