OPC UA GDS - no registration with the UaGDS after a controller power-up

     

Fixed from:
Lenze controller c5x0 V1.14 and c430 V1.14
 
Behavior of the new version:
Automatic registration with the UaGDS takes place after switching controller mains.

Description of the behavior:
There is no registration with the UaGDS after controller mains switching, although this is configured.

Conditions under which the behavior occurs:
Switching the controller to mains.

Affected products:
Lenze controller c5x0 V1.14 and c430 V1.14
UaGDS V1.1.1 (software tool from United Automation)

Short-term measure, recommendations, evaluation:
Registration takes place after the OPC UA server restart.