i950 from device size 6 (22 kW, 30 kW): Displayed energy values under parameter 0x2DA:003 not plausible (fixed from V01.14.00)

Fixed as of:
Servo inverter i950 FW:  from  V01.14.00

Behavior of the new version:
Under parameter 0x2DA3:003, plausible energy values are now displayed under parameter 0x2DA3:003.

 
Description of behavior;
The energy display under parameter 0x2DA3:003 shows incorrect values in certain constellations.

Under what conditions does the behavior occur?

  • i950 from device size BF6 (22 kW, 30 kW),
  • for which phase voltage measurement is active  AND
  • the inverter characteristic curve (WRK) function is activated (0x2947: 018=[1]).

Affected products;
Servo Inverter i950 FW

Short-term measures / Evaluation / Recommendations
Deactivation of theinverter characteristic curve function (0x2947=018=[0]),
unless this functionality is absolutely necessary for other functions.

[Automatic Translation]
URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202500264/1/