i950 230V devices: Suitable interference suppression filter: Low-leakage filter, 1.50kW, 17.0A, 1x230V LL (I0FAE215B100L0001S)

Function extension:
The following interference suppression filter can now be used for the single-phase 230V devices of the Servo Inverter i950 series: 

  • Low-Leakage (LL) 1.5kW 17A 1x230V LL  (I0FAE215B100L0001S) 
  • Mains voltages 1x 230/240V
  • for substructure and adjacent mounting.

Technical requirements:

  • Rated current based on 40°C ambient temperature

Disturbance filter expression

INENN

                         Assignment Servo i950

fSW

BF3 1x 230/240V: LL

17.0A

    0.37kW, 0.55kW, 0.75kW, 1.5kW

2kHz ... 16kHz

  • tension:

Net

                                                         TN, TT

Phase

                                                       1/N/PE

Designated voltage      (AC)

                                                  230/240V

Net frequency

                                            45Hz ... 65Hz

  • High-frequency interference emission and residual current

When installing a filter, both IT screws on the servo inverter i950 must be removed.

  • Case

Type of protection

     IP20    according to EN 60529    Type 1    NEMA

  • Line-bound emission

Compliance with the limit values for the interference voltage at the mains terminal according to category C1 and C2 in each case with shielded motor cable in accordance with EN 61800-3.

Distortion filter                              Switching frequencies

Category and motor cable length shielded

BF3 1x 230/240V: LL                    2kHz ... 8kHz
                                                        2kHz ... 4kHz
                                                       2kHz ... 16kHz

                              C1                             3 m
                              C1                            5 m
                              C2                            5 m

  • Error current

Compliance with the residual current for operation on residual current circuit breaker (RCCB) type B with a rated residual current of 30mA. The limit value is 33%.

Disturbance filter

Trigger current and motor cable length shielded

BF3 1x 230/240V: LL                   2kHz ... 8kHz
                                                       2kHz ... 16kHz

                             8%                            3 m
                           10%                            5 m

  • touch current

Proof that the touch current is less than 3.5mA.

Disturbance filter

 

BF3 1x 230/240V: LL                   2kHz ... 16kHz
                                                       2kHz ... 16kHz

                       3.4 mA                            3 m
                       3.4 mA                            5 m

  • Mounting

Installation location

Control cabinet

Installation position

Hanging, mounted behind frequency inverter,or mounted next to the frequency inverter


Conformity, Explanations and evidence:
  • CE conformity
  • RoHS
  • China-RoHS
  • UL certificate (in progress)
  • UKCA conformity
  • REACH

Included in the following products:
Servo inverter i950 - all single-phase 230V devices, regardless of firmware version:

Application:
Use of the i950 230V devices in areas with high requirements for the interference category (C1, C2).


[Automatic Translation]