FAST UI Runtime - Preloading: A limit error is displayed when the project starts
Corrected from:
Behavior of the new version:
Description of behavior: When the project is started, a "max error" limit is incorrectly displayed if preloading has been enabled on the page. New entries in NumericVarIn are not accepted via the visualizer, but they can be written from the PLC side.
Conditions under which the behavior occurs:
Place NumericVarIn on a page
Connect the variable including limits
Enable the " Is limit check enabled " and " Show error text" options inthe Properties window