i950 ES and PLC-Designer V4: Error message occurs after downloading the project (fixed with device description from V01.11.00.12)

Removed from:
i950 Safety-Extended with PLC-Designer-V4 and device description as of V01.11.00.12
Behavior of the new version:
i950 ES and PLC-Designer-V4: 
Downloading the project to the device is now possible without error messages possible.


Description of the behavior:
When downloading a project created with PLC-Designer V4 with an i950 Safety-Extended servo inverter and activated Web-Visu, error messages occur (unresolved references).

conditions under which the behavior occurs:

  • Program download with PLC-Designer V4 and 
  • Use of an i950 Safety-Extended and
  • Use of the Web-Visu functionalities

Affected products:
i950 Safety-Extended with PLC-Designer-V4 and device description 

V01.11.00.11
Short-term measures, Recommendations, Rating:

[Automatic Translation]
URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202500159/1/
Contact form