i950ES: Safe parameter set: Version and displayed version in the parameter dialog are different (fixed from V01.04.00)

Fixed from:
i950 ES Safety Firmware V01.04.00

Behavior of the new version:
The version of the safe parameter set and the displayed
parameter set version in the parameter dialog index 0x2114:001 can no longer be different, as the version adjustment is now done automatically.



Description of behavior:
When using the safe parameterization editor in the PLC Designer, it has been noticed that the setting of the "version of the safe parameter set" may not match the parameter set version in the parameterization dialog.

conditions under which the behavior occurs:
The case occurs when the parameter set version of the safe parameter set is increased, e.g. from V01.01 to V01.03.
In this case, the safe index 0x2114:001 in the parameterization dialog still shows the value "i950 ES V01.01" and must be set manually to the correct value "i950 ES V01.03".

In comparison to the parameterization dialog in the Easy-Starter, the version adjustment is carried out automatically, or the selection of the safe parameter set version is limited to the safe parameter set version set in the parameterization dialog.
Affected products:
i950 ES Safety Firmware

Short-term measures, Recommendations, Rating:
Use Easy Starter to generate the safe parameter set.

When using the PLC Designer, make sure that the safe index 0x2114 Sub001 is manually adapted to the parameter set version used.


[Automatic Translation]