Description of the behavior:
A firmware download from the Lenze Motion Controller to the i950 via FoE is not performed successfully.
Under what conditions does the behavior occur?
- The device description of an i950 EtherCAT slave in the PLC Designer project of the Lenze Motion Controller was updated at some point in the past from a version lower than V01.08 to V1.10 or higher
- A firmware download is activated in the 'Firmware/Parameter set' tab of the i950 EtherCAT slave.
- The version of the Lenze Motion Controller is V1.12 or higher
Affected products:
All PLC Designer versions
Short-term measures / evaluation / recommendations:
If the i950 EtherCAT slave is not updated to V01.10 or greater, but is newly inserted, then the behavior does not occur