I/O mapping cannot be imported from CSV file

Corrected from:
-
Behavior of the new version:
-


Description of behavior:
The context menu command 'Import mappings from CSV' does not import the I/O mapping from a previously created CSV file importiert . No error message is displayed during import.

Conditions under which the behavior occurs:
The PLC Designer can import the I/O mapping from a CSV file if

  • the CSV file was created with PLC Designer V3 and
  • the list separator set via the Windows system language is a comma (,).
Affected products:
PLC Designer from V4.0

Short-term measures, Recommendations, Rating:
After creating the CSV file, manually replace the list separator with the one set in the Windows system language.

[Automatic Translation]


URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202500058/1/