L_IPAP_ParameterWrite: Error message when writing parameters of type 'String' (fixed with V1.13)

Removed from:
Cabinet Controller c430 V1.13
Cabinet Controller c520 V1.13
Cabinet Controller c550 V1.13
Behavior of the new version:
The 'L_IPAP_ParameterWrite' function block from the 'L_IPAP_ParameterManagerAccess' library can also be used to successfully write parameters of type 'String'.

Description of the behavior:

When writing a parameter with the function block 'L_IPAP_ParameterWrite' from the 'L_IPAP_ParameterManagerAccess' library, the error message appears:
ERR_ValueSizeExceeded

The pararmeter is not changed.

Conditions under which the behavior occurs:

The behavior described above occurs when a parameter of type 'String' is written by the function block 'L_IPAP_ParameterWrite'.

Parameters of type 'String' with exactly the length 6 are not affected by this function restriction.

Affected parameters are:

  • 0x2001:000 device name
  • 0x2381:001...008 Profinet parameters (station name and IuM data)
  • 0x5913:010, :020, :030, :040 Firewall protocol name

Affected products:
Cabinet Controller c430 from V1.11
Cabinet Controller c520 from V1.11
Cabinet Controller c550 from V1.11

Short-term measures, Recommendations, Rating:
Enter the values for the relevant parameters directly via the parameter list in EASY Starter or PLC Designer.

[Automatic Translation]