L_IE1P_SetError: i950 does not support the severity 'Fault'
Corrected from:
-
Behavior of the new version:
-
Description of behavior: If an error is triggered via the function module L_IE1P_SetError or L_IE1P_SetErrorSingle, the reaction set at the eReaction input is executed, but the message:
can no longer be acknowledged
cannot be diagnosed via FB L_IE1P_ReadActualError or object 0x2010
Conditions under which the behavior occurs: The Severity 'Fault' [30] is not fully supported by the Servo Inverter i950. If an event with this severity is triggered via the function block L_IE1P_SetError or L_IE1P_SetErrorSingle, the behavior described above can be observed.