i950: Switching from TA-CiA402 to TA-User leads to timeout error message - however, switching is not necessary to load another TA into the unit (no change planned)

Corrected from:
Servo Inverter i950 FW: (no change planned)
 
Response of the new version:
No change to the software is planned to adjust the behaviour, because switching to TA-User is not necessary in practice, see notes under short-term measures. 

 
What happens?
When switching the application to "TA User" (0x4000 = 10000), a timeout error message occurs under certain conditions.

When does the behaviour occur?
  • No user application is available / stored on the SD card yet and
  • it is switched to the application selection "TA User" (0x4000 = 10000), e.g. via the tab 'Settings' in the EasyStarter.
Which products are affected?
Servo Inverter i950 FW
 
Short-term measures / evaluation / recommendations:
In principle, it is not necessary to first switch to the "TA User" setting before loading a user application.
PLC Designer:
If an application/boot project is transferred to the i950, it is automatically switched to "TA User" (0x4000 = 10000).
Easy Application Loader:
If an application is transferred to the i950, the transferred parameter set already contains the correct TA selection.


Automatic Translation

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202200341/1/