User administration: Password cannot be changed

Corrected from:
-

Response of the new version:
-
 
Response of the new version:
If a user logs in to the controller while the user administration is active and then attempts to change the password of the device user, the prompt to log in again first appears. After entering the user name and password, the dialogue for changing the password appears, but it reacts to the password change with the following message:
You are not logged in to the machine.

It is not possible to change the password.
 
When does the behaviour occur?
The behaviour occurs when a new user is created with PLC Designer while user administration is active and the option 'User can change password' is set.
 
Which products are affected?
PLC Designer from V3.26
Cabinet Controller c520 from V1.9
Cabinet Controller c550 from V1.9

Short-term measures / evaluation / recommendations:
Additionally set the option 'Password must be changed at first login' when creating a new user.


Automatic Translation

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202200282/1/