Corrected from:
-
Response of the new version:
What happens?
If the value of a user parameter defined in the PLC project is changed in the EASY Starter, it is not adopted by the controller.
If the same user parameter is changed via the parameter list in the PLC Designer, the value is adopted.
When does the behaviour occur?
The behaviour described above occurs when the variable for which the user parameter was created has the data type SINT.
Which products are affected?
Cabinet Controller c300 from V3.8
Cabinet Controller 3200C from V3.0
Panel Controller p300 from V3.8
Panel Controller p500 from V3.2
Short-term measures:
Avoid creating user parameters for variables that have the data type SINT.
Evaluation / recommendations:
Due to this function restriction, the value of user parameters with the type SINT cannot be changed with the EASY Starter.