Persistent variables have default values (corrected from V1.9)

Corrected from:
Cabinet Controller c520 V1.9
Cabinet Controller c550 V1.9

Response of the new version:
If the controller is switched off after an OnlineChange without updating the boot application, the persistent data from before the power was switched off is retained and is not reset to default values.
 
What happens?
After a start of the controller, the persistent data (incl. the data for the position reconstruction of the connected axes) have default values.
 
When does the behaviour occur?
The behaviour occurs when the boot application is not updated after an OnlineChange and then the controller is switched off.
 
Which products are affected?
Cabinet Controller c520 from V1.5
Cabinet Controller c550 from V1.5
Cabinet Controller c750 from V1.5

Short-term measures:
Either update the boot application immediately with the OnlineChange (via the corresponding dialogue) or create a new boot application online after the OnlineChange before switching off the controller.