i950 ES: Functional Safety over EtherCAT (FSoE) via EtherCAT fieldbus modul (from V01.02.03)
Funktions-Erweiterung:
Function extension: The i950 ES supports the transmission of safe information via the "Safety over EtherCAT" (FSoE) protocol according to the specification "ETG.5100", version 1.2.0. This enables an i950 with Extended safety (ES) to be integrated in the EtherCAT network on an FSoE Safety Controller (Lenze or Beckhoff).
The following topologies are currently supported with Safety Firmware V01.02.03:
FSoE via EtherCAT fieldbus modul
Lenze
Controller is EtherCAT master, c250-S is FSoE master
Beckhoff
PLC is EtherCAT master, TwinSAFE is FSoE master
i950
ES (Extended Safety) as CiA 402 Base (0x4000 = 0)
Not
possible due to missing field bus module support
i950
ES (Extended Safety) as CiA 402 Advanced (0x4000 = 1)
From Device V01.04.01, SD card is nessecary
i950
ES (Extended Safety) with TA or Soft PLC program (0x4000 > 1)
From Device V01.04.01, SD card is nessecary
Contained in which products? Servo inverter i950 Safety FW: from V01.02.03
Application:
i950 Extended Safety Integration in topologies with FSoE Safety controllers.